Applications
- Solar Systems and UPS
- Telecommunication system
- Alarm system
Warrant Prerequisites
24v Inverter Parameter Settings
- Floating charging voltage : 27.2v
- Bulk charging voltage : 28.4v
- Low DC cut-off voltage 23.6Â Â or 24v
48v Inverter Parameter Settings
- Floating charging voltage : 54.4v
- Bulk charging voltage : 56.8v
- Low DC cut-off voltage 47.2Â Â or 48v
10.5v is the theoretical 100% discharge end voltage of the 12v battery
The best discharge depth of the gel battery is 50% to 60%
Please adjust the inverter parameters to these standards before use.Â