The E-guard NML (Long life) range is a gel design with an AGM separator (commonly referred to as Lead Crystal) and is designed for solar and alternative energy systems.
Typical Applications
Solar Energy Systems.
Wind Energy Systems.
Power Utility.
UPS/EPS.
Electrical Specifications
Design floating Life @ 20°C
10 years.
Nominal Capacity @ 25°C
20 hour rate 5.32A to 1.75Vpc 106.4 Ah.
10 hour rate 10.38A to 1.75Vp 103.8 Ah.
Internal Resistance (Fully charged battery @ 25°C)
5 mΩ.
Max. Discharge Current @ 25°C
1000 A (5S).
Charge Methods (Constant voltage charge @ 25°C)
Cycle Use: 14.7 ~ 14.9V Max.
Current: 27A.
Standby Use: 13.6 – 13.8V.
Operating Temperature Range
Discharge: -15 ~ 50°C.
Charge: 0 ~ 50°C.
Storage: -15 ~ 50°C.
Recommended Operating Temp: 15 ~ 25°C.
Self-Discharge
3% of capacity declined per month @ 20°C (68°F).
Dimensions and Weight
L x W x H: 327mm x 172mm x 216mm
Total Height: 221mm.
Weight: 31.7Kg.