Product Range: SENTRON
Voltage Rating VAC: 230V
Current Rating: 40A
No. of Poles: 2 Pole
Overload Current: 500A
Model
product brand name SENTRON
product designation RCCB
design of the product Instantaneous
General technical data
number of poles 2
size of installation devices / according to DIN 43880 1
mechanical service life (switching cycles) / typical 10 000
short-circuit current / of series fuse / maximum permissible 63 A
short-circuit current rating 10 kA
switching function / short-term delayed No
overvoltage category III
Supply voltage
supply voltage / for testing equipment / minimum 195 V
value range / of the supply voltage frequency 50 Hz
value range / of the operating frequency 50 Hz
value range / of the supply voltage / at AC 230 V
Protection class
protection class IP IP20, if the distribution board is installed, with connected conductors
Switching capacity
switching capacity current
– according to IEC 61008-1 / rated value 0.5 kA
Dissipation
power loss [W]
– for rated value of the current / at AC / in hot
operating state / per pole
2.6 W
– maximum 5.2 W
Current
tripping fault current / rated value 30 mA
operational current
– at 40 °C / rated value 40 A
– at 45 °C / rated value 38.1 A
– at 50 °C / rated value 35.59 A
– at 55 °C / rated value 32.29 A
– at 60 °C / rated value 28.19 A
– at 65 °C / rated value 23.3 A
– at 70 °C / rated value 17.6 A
– at AC / rated value 40 A
residual current type A
let-through current / permissible 5 200 A
details
product feature / silicon-free Yes
product extension / installable / supplementary devices Yes
Connections
connectable conductor cross-section / solid
– minimum 0.75 mm²
– maximum 35 mm²
connectable conductor cross-section / stranded
– minimum 0.75 mm²
– maximum 35 mm²
tightening torque / with screw-type terminals
– minimum 2.5 N·m
– maximum 3 N·m
position / of power supply cord top or bottom
What’s in the box
1 x Circuit Breaker
Reviews